0

Out of 0 Ratings

Owner's of the GE Network Hardware 15A ARC FAULT BREAKER gave it a score of 0 out of 5. Here's how the scores stacked up:
  • Reliability

    0 out of 5
  • Durability

    0 out of 5
  • Maintenance

    0 out of 5
  • Performance

    0 out of 5
  • Ease of Use

    0 out of 5
of 42
 
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 3 Pole, Total Main Wire Size
Ampere 1” 1” 1” 1-pole Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Front Type Type Number Cu-Al Ground Kit Number
200 30 14 10 30 Combination Top 12 1-250 (Cu), TGK32 (order separately) TM30420C
Flush/Surface 2/0-250 (Al)
Front
200 30 14 10 30 Combination Bottom 12 1-250 (Cu), TGK32 (order separately) TM30420CB
Flush/Surface 2/0-250 (Al)
Front
200 42 20 14 42 Combination Top 14 1-250 (Cu), TGK42 (order separately) TM42420C
Flush/Surface 2/0-250 (Al)
Front
200 42 20 14 42 Combination Bottom 14 1-250 (Cu), TGK42 (order separately) TM42420CB
Flush/Surface 2/0-250 (Al)
Front
225 42 20 14 42 Combination Top 15 1-300 (Cu), (2) TGL2 (order separately) TM42422C
Flush/Surface 2/0-300 (Al)
Front
225 42 20 14 42 Combination Bottom 15 1-300 (Cu), (2) TGL2 (order separately) TM42422CB
Flush/Surface 2/0-300 (Al)
Front
1
Also UL Listed for three-phase, four-wire 240/120 Volts Hi leg delta and three-phase, three-wire 240 Volts ac branch breakers installed.
Outdoor (NEMA 3R) Enclosure
Main 1 Pole, 2 Pole, 3 Pole, Total Main Wire Size
Ampere 1” 1” 1” 1-pole Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Type Number Cu-Al Ground Kit Number
100 18 8618 Top R4 6-1/0 (Cu), TGK24 (order separately) TM18410R
4-1/0 (Al) TGK32 (order separately)
125 30 14 10 30 Top R7 1-3/0 (Cu), TGK32 (order separately) TM30412R
2/0-3/0 (Al)
150 24 12 8 24 Top R6 1-3/0 (Cu), TGK32 (order separately) TM24415R
2/0-3/0 (Al)
150 30 14 10 30 Top R7 1-3/0 (Cu), TGK32 (order separately) TM30415R
2/0-3/0 (Al)
200 30 14 10 30 Top R7 1-250 (Cu), TGK32 (order separately) TM30420R
2/0-250 (Al)
200 42 20 14 42 Top R8 1-250 (Cu), TGK42 (order separately) TM42420R
2/0-250 (Al)
225 42 20 14 42 Top R8 1-300 (Cu), TGK42 (order separately) TM42422R
2/0-300 (Al)
Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.
Section 1
Load Center
3PH
Main Breaker
Indoor NEMA 1
Load Centers and Circuit Breakers
PowerMark Plus
Load Centers
Three-Phase, Four-Wire, 208Y/120 Vac
1
Main Circuit Breaker Factory Installed
1-16
BuyLog
Catalog
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Load Center
3PH
Main Breaker
Outdoor NEMA 3R